Continuous monitoring for water and wastewater treatment

Agrinovo puts sensors at each control point of a treatment line, from disinfection residual to aeration oxygen, sludge concentration and effluent quality. Every reading reaches the dashboard and the operators' phones around the clock, through a cellular controller that runs on mains, batteries or solar.

Where a treatment line needs a reading, not a grab sample

A laboratory sample tells you what the water was when it was taken. A sensor in the water tells you what it is now, and what it did overnight. Three points on most treatment lines decide whether the plant is in control.

Disinfection residual

Too little ozone or chlorine dioxide and the water is under-treated; too much and you waste oxidant and risk exceeding a limit. In US drinking water, for example, the EPA sets a maximum residual disinfectant level of 0.8 mg/L for chlorine dioxide and a limit of 1.0 mg/L for its by-product chlorite. The O3-100 reads dissolved ozone from 0.00 to 20.00 mg/L (±0.02 mg/L) and the ClO2-100 reads chlorine dioxide from 0.00 to 20.00 mg/L (±0.1 mg/L), with the ORP-110 as the fast indicator beside them.

Aeration and nutrient removal

Aeration is usually the largest energy user in a plant: the US EPA, citing the Water Environment Federation, puts it at 25 to as much as 60 percent of total plant energy use, and EPA training material gives 1.0 to 2.0 mg/L as the desired average oxygen in most activated sludge reactors. A self-cleaning DO-130 oxygen probe in the basin, ammonium and nitrate electrodes, and the MLSS-110 sludge sensor (0 to 50,000 mg/L) give the operator the numbers that air and sludge decisions are made on.

Effluent and reuse

The COD-130 reads COD by UV absorption (0-300 or 0-1500 mg/L) and also reports BOD, TOC and turbidity values, the TUR-110 reads 0.01 to 3000 NTU, and the SS-130 reads suspended solids. Where treated water goes to irrigation, conductivity, pH, nitrate and chloride follow it to the reservoir. The FAO guidelines for irrigation water quality start restricting use at a conductivity of 0.7 dS/m.

How a treatment monitoring point is installed

  1. A sensor at the point of control

    Immersed in the basin or contact tank on a bracket, or fitted into the pipe. The COD, turbidity, suspended solids, sludge and oxygen sensors clean themselves with an automatic wiper or brush, for basins nobody wants to clean by hand, and the cable runs to a controller mounted at a dry, safe spot.

  2. A controller that reports on its own

    The Omni Genesis reads up to four sensors and sends every reading over the cellular network, on mains, batteries or solar, so a pump station, a reservoir or a small plant needs no network or control room. Where the plant already has a control system, the same sensors can report into it as well; your control contractor will find the technical details on our integration page.

  3. A range and a delay for each point

    On the dashboard each probe gets a name, a minimum, a maximum and the time a reading may stay outside them before an alert opens, so a short spike during backwashing or a cleaning cycle does not raise one.

Guides: dissolved ozone monitoring · chlorine dioxide monitoring · COD and suspended solids · cooling tower corrosion

What you see and when you hear about it

Every point on one screen

Each probe appears with its current reading, its range and its history, grouped by site, so a plant, its pump stations and its reuse reservoir sit on the same dashboard.

An alert that keeps asking

When a reading stays out of range longer than allowed, the users on the account get an app notification. It repeats every two hours by default until someone reads it, a second notice follows when the reading is back in range, and a probe marked as critical comes through quiet hours.

A failed probe is not a good reading

The controller reports a disconnected or short-circuited sensor as a fault instead of a plausible number, an offline alert opens if a controller stops reporting, and a low battery raises its own alert. Rules on the controller can also switch a valve or a dosing pump through a relay, and keep working if the connection drops.

Where it is installed

Small and rural wastewater plants

Aeration oxygen, sludge concentration and effluent quality at plants without a full-time operator on site.

Ozone and chlorine dioxide disinfection

Residual control in drinking water, food and beverage plants, aquaculture recirculation and process water.

Treated wastewater for irrigation

Conductivity, pH, nitrate, ammonium, chloride and turbidity at the reservoir and the farm inlet.

Industrial effluent and pretreatment

COD, suspended solids, pH and flow before discharge to a sewer or a receiving water.

Cooling towers and process water

Conductivity, pH, ORP and corrosion rate on cooling and process loops.

Pump stations and remote reservoirs

Sites with no network and often no mains power, on a cellular controller with batteries and solar.

Probes for treatment monitoring

Dissolved ozone (O3-100) 0.00-20.00 mg/L, ±0.02 mg/L, IP68
Chlorine dioxide (ClO2-100) 0.00-20.00 mg/L, ±0.1 mg/L, electrochemical
ORP (ORP-110) -1999 to +1999 mV, ±3 mV, PTFE body, IP68
Dissolved oxygen (DO-130) Fluorescent, automatic cleaning brush, salinity and pressure compensation
Sludge and suspended solids (MLSS-110, SS-130) 0-50000 mg/L, ±10% or 10 mg/L, self-cleaning, IP68 (MLSS-110)
COD (COD-130) UV absorption, 0-300 or 0-1500 mg/L, ±10%, also BOD, TOC and turbidity values, self-cleaning
Turbidity (TUR-110) 0.01-3000 NTU, ±5% or ±0.5 NTU, self-cleaning, IP68
Ammonium, nitrate, chloride (NH4-100, NO3-100, Cl-100) Ion-selective electrodes, ±5% F.S.
pH and conductivity (PH-110, EC-100) pH 0-14.00, ±0.02 pH; conductivity 0.2 µS/cm to 100 mS/cm, ±1.0% F.S.
Flow (EMF-200) Insertion electromagnetic, DN100-DN3000, ±1.5% of reading at ≥1 m/s
Reporting Omni Genesis over the cellular network, dashboard and phone alerts; can also feed an existing control system

Questions about treatment monitoring

Can sensors in the water replace laboratory tests?

No, and they are not meant to. Compliance samples follow your permit or standard and its laboratory methods. Continuous sensors fill the hours between samples, show trends and excursions as they happen, and are checked against the laboratory results to stay honest.

Which parameters matter in an activated sludge basin?

Dissolved oxygen first, because it drives both treatment and the energy bill: EPA training material gives 1.0 to 2.0 mg/L as the desired average reactor oxygen for most activated sludge and notes that a reactor above 2.0 mg/L is likely wasting energy. Ammonium and nitrate show whether nitrification and denitrification are complete, and MLSS, 1,500 to 3,500 mg/L in the same EPA ranges, shows the sludge inventory.

How is ozone or chlorine dioxide residual monitored continuously?

With a residual probe in or after the contact tank: the O3-100 for dissolved ozone and the ClO2-100 for chlorine dioxide, each reading 0.00 to 20.00 mg/L, with an ORP probe beside them as the fast indicator. EPA guidance notes that ozone residual dissipates rapidly and varies through a contactor, so the probe position matters, and that for disinfection credit the ozone residual is determined by the indigo colorimetric method; the sensor tracks the process between those tests.

What should treated wastewater for irrigation be checked for?

Salinity, specific ions and nitrogen first. The FAO irrigation water quality guidelines put a slight to moderate restriction on use at a conductivity of 0.7 to 3.0 dS/m and a severe one above 3.0, give chloride and sodium thresholds in milliequivalents per litre, and put nitrate-nitrogen at 5 to 30 mg/L for slight to moderate restriction, counting ammonium and organic nitrogen in wastewater. For continuous monitoring, the EC-100, PH-110, NO3-100, NH4-100, Cl-100 and TUR-110 cover conductivity, pH, nitrate, ammonium, chloride and turbidity. Boron and microbiological parameters are laboratory tests.

Can the readings also go into our existing control system?

Yes. The same sensors can report to the Agrinovo dashboard, to the plant's existing control system, or to both. Your control contractor will find the technical details on our page for integrators.

Can the system run at a remote site without power?

The Omni Genesis controller runs on rechargeable batteries with a 6 to 32 V DC solar input and reports over 4G-LTE, so a reservoir or pump station needs no mains or network. Self-cleaning probes draw more power than plain ones, so tell us which probes the site needs and we will size the power with you.

Tell us about your treatment line

What the plant treats, which points you need to watch, whether there is a control system on site, and who should get the alert. We will match the sensors to the points.