TVOC-100 with Arduino, ESP32, Raspberry Pi and Python

How to wire the TVOC-100 RS485 Air Quality Sensor to your own microcontroller or computer and read it over RS485 Modbus RTU. The tables are the ones in the datasheet, and both code examples are run against the datasheet example frame before this page is published.

Product page Datasheet (PDF) Datasheet (Markdown) Arduino sketch (.ino) Python script (.py)

TVOC-100 RS485 Air Quality Sensor

Connecting the TVOC-100

The probe is an RS485 device, so it needs a transceiver between it and your board. On a computer or a Raspberry Pi that is a USB to RS485 adapter. On a microcontroller it is a MAX485-type module on a hardware serial port. Power the probe from a supply within the voltage range in the table and join its ground to the ground of the transceiver.

Terminal Function Description
V+ Power Power Supply (5-12 V DC)
GND Ground Power Ground
A+ RS485-A Data+
B- RS485-B Data-

Python example (Raspberry Pi, Linux, macOS, Windows)

The script needs only pyserial. It builds the Modbus request itself, checks the CRC of the reply and prints one reading every five seconds. On Windows pass the COM port as the argument.

#!/usr/bin/env python3
"""Read the Agrinovo TVOC-100 over RS485 Modbus RTU.

Works on a Raspberry Pi or any computer with a USB to RS485 adapter.
Install the serial library once:  pip install pyserial
Run:  python3 tvoc_100.py /dev/ttyUSB0
"""
import struct
import sys
import time

import serial

PORT = sys.argv[1] if len(sys.argv) > 1 else "/dev/ttyUSB0"
ADDRESS = 0x01  # the sensor's Modbus address


def crc16(frame: bytes) -> bytes:
    crc = 0xFFFF
    for byte in frame:
        crc ^= byte
        for _ in range(8):
            crc = (crc >> 1) ^ 0xA001 if crc & 1 else crc >> 1
    return struct.pack("<H", crc)


def read_registers(port, address, function, start, count):
    request = struct.pack(">BBHH", address, function, start, count)
    port.reset_input_buffer()
    port.write(request + crc16(request))
    reply = port.read(5 + 2 * count)
    if len(reply) >= 5 and reply[1] == function | 0x80:
        raise IOError(f"sensor returned Modbus error {reply[2]}")
    if len(reply) != 5 + 2 * count or crc16(reply[:-2]) != reply[-2:]:
        raise IOError("no valid reply from the sensor")
    return reply[3:-2]


def read_probe(port):
    data = read_registers(port, ADDRESS, 0x03, 0x0003, 2)
    return {
        "tvoc":           struct.unpack(">H", data[0:2])[0],  # ppb
        "co2_equivalent": struct.unpack(">H", data[2:4])[0],  # ppm
    }


if __name__ == "__main__":
    with serial.Serial(PORT, 9600, bytesize=8, parity="N", stopbits=1, timeout=1) as port:
        while True:
            print(read_probe(port))
            time.sleep(5)

Arduino example (Uno, Mega, ESP32, ESP8266, MKR, Pico)

The sketch uses the Agrinovo library: in the Arduino IDE open Sketch > Include Library > Manage Libraries and install "Agrinovo". The library picks the serial port for your board, and the pins are listed at the top of AgrinovoDefaultPort.h. DE and RE of the transceiver go to one output pin.

// Agrinovo TVOC-100 TVOC air quality sensor
// Prints TVOC and CO2 equivalent every 5 seconds.
//
// Sensor terminals
//   V+   supply +, 5-12 V DC
//   GND  supply ground, joined to the board's ground
//   A+   RS485 A
//   B-   RS485 B
//
// The board talks to the sensor through an RS485 transceiver (MAX485 or
// similar). AgrinovoDefaultPort.h lists the serial pins used on each board.
//
// https://agrinovo.io/products/sensors/environmental/tvoc-100-rs485-air-quality-sensor/

#include <Agrinovo.h>
#include <AgrinovoDefaultPort.h>

const int DE_PIN = 4;  // transceiver DE and RE, tied together

AgrinovoBus bus(AGRINOVO_PORT, DE_PIN);
AgrinovoTVOC100 sensor(bus);  // Modbus address 1

void setup() {
  Serial.begin(115200);
  agrinovoPortBegin(9600);
  bus.begin();
}

void loop() {
  if (sensor.read()) {
    Serial.print("TVOC: ");
    Serial.print(sensor.tvoc(), 0);
    Serial.println(" ppb");
    Serial.print("CO2 equivalent: ");
    Serial.print(sensor.co2Equivalent(), 0);
    Serial.println(" ppm");
  } else {
    Serial.println(sensor.errorText());
  }
  delay(5000);
}

What the examples read

Both examples send one request, function 0x03, 2 registers from 0x0003, and decode these values:

Value Unit Register Encoding
TVOC ppb 0x0003 Unsigned 16-bit integer, scaled
CO2 equivalent ppm 0x0004 Unsigned 16-bit integer, scaled

Other Modbus tools

The same request works from any Modbus RTU master: pymodbus, minimalmodbus, Node-RED, LabVIEW, a PLC or a third-party data logger with a Modbus port. Use the serial settings, function code and register addresses above.

Logging without writing code

The Omni Genesis controller reads the TVOC-100 and sends the readings to the Agrinovo cloud over the cellular network, where they can be exported or read through the cloud API.

Datasheet reference

Specifications

Parameter Specification
TVOC Range 0-60000 ppb
TVOC Accuracy ±1 ppb (0-2008 ppb), ±6 ppb (2008-11110 ppb), ±32 ppb (11110-60000 ppb)
CO2eq Range 400-60000 ppm
CO2eq Accuracy ±1 ppm (400-1479 ppm), ±3 ppm (1479-5144 ppm), ±9 ppm (5144-17597 ppm), ±31 ppm (17597-60000 ppm)
Resolution 1 ppb TVOC, 1 ppm CO2eq
Output RS485, Modbus-RTU
Bus Length Up to 1200 m
Supply Voltage 5-12 V DC
Power Consumption <0.1 W
Protection Built-in surge protection
Placement Indoor, non-condensing

CO2eq is an equivalent-CO2 air quality value calculated from the VOC measurement. For direct CO2 measurement, pair with a dedicated CO2 sensor.

Communication Settings

Parameter Value
Protocol Modbus-RTU
Baud Rate 9600 bps (default); 1200, 2400, 4800, 19200 selectable
Data Bits 8
Parity None
Stop Bits 1
Error Check CRC-16
Default Address 0x01

Multiple sensors share one RS485 bus, each with a unique address (1-247).

Register Map

Measurement Registers (Function 0x03 or 0x04)

Address Description Unit
0x0003 TVOC 1 ppb
0x0004 CO2eq 1 ppm

A register value of 0x8000 indicates a sensing element read error.

Configuration Registers (Function 0x03/0x04 read, 0x06/0x10 write)

Address Description Values
0x0064 Device Address 1-247, default 1
0x0065 Baud Rate 0: 1200, 1: 2400, 2: 4800, 3: 9600, 4: 19200

Reading Data

Read TVOC and CO2eq (2 registers from 0x0003):

Request:  01 03 00 03 00 02 34 0B
Response: 01 03 04 00 7D 02 62 EA A2

Decoding:

Value Hex Decimal Result
TVOC 0x007D 125 125 ppb
CO2eq 0x0262 610 610 ppm

Address Configuration

Change Address (0x01 → 0x02)

Write to register 0x0064:

01 06 00 64 00 02 49 D4

Broadcast Discovery

With only one sensor on the bus, address 0xFF reads or writes regardless of the configured address. Read the current address:

FF 03 00 64 00 01 D0 0B

Set the address to 0x02 without knowing the current one:

FF 06 00 64 00 02 5C 0A

Change Baud Rate (set 9600)

Write to register 0x0065:

01 06 00 65 00 03 D9 D4

Revision History

Rev Date Changes
1.0 June 2026 Initial release
1.1 August 2026 Layout revision
1.2 October 2026 New layout