TVOC-100 with Arduino, ESP32, Raspberry Pi and Python
How to wire the TVOC-100 RS485 Air Quality Sensor to your own microcontroller or computer and read it over RS485 Modbus RTU. The tables are the ones in the datasheet, and both code examples are run against the datasheet example frame before this page is published.
Product page Datasheet (PDF) Datasheet (Markdown) Arduino sketch (.ino) Python script (.py)
Connecting the TVOC-100
The probe is an RS485 device, so it needs a transceiver between it and your board. On a computer or a Raspberry Pi that is a USB to RS485 adapter. On a microcontroller it is a MAX485-type module on a hardware serial port. Power the probe from a supply within the voltage range in the table and join its ground to the ground of the transceiver.
| Terminal | Function | Description |
|---|---|---|
| V+ | Power | Power Supply (5-12 V DC) |
| GND | Ground | Power Ground |
| A+ | RS485-A | Data+ |
| B- | RS485-B | Data- |
Python example (Raspberry Pi, Linux, macOS, Windows)
The script needs only pyserial. It builds the Modbus request itself, checks the CRC of the reply and prints one reading every five seconds. On Windows pass the COM port as the argument.
#!/usr/bin/env python3
"""Read the Agrinovo TVOC-100 over RS485 Modbus RTU.
Works on a Raspberry Pi or any computer with a USB to RS485 adapter.
Install the serial library once: pip install pyserial
Run: python3 tvoc_100.py /dev/ttyUSB0
"""
import struct
import sys
import time
import serial
PORT = sys.argv[1] if len(sys.argv) > 1 else "/dev/ttyUSB0"
ADDRESS = 0x01 # the sensor's Modbus address
def crc16(frame: bytes) -> bytes:
crc = 0xFFFF
for byte in frame:
crc ^= byte
for _ in range(8):
crc = (crc >> 1) ^ 0xA001 if crc & 1 else crc >> 1
return struct.pack("<H", crc)
def read_registers(port, address, function, start, count):
request = struct.pack(">BBHH", address, function, start, count)
port.reset_input_buffer()
port.write(request + crc16(request))
reply = port.read(5 + 2 * count)
if len(reply) >= 5 and reply[1] == function | 0x80:
raise IOError(f"sensor returned Modbus error {reply[2]}")
if len(reply) != 5 + 2 * count or crc16(reply[:-2]) != reply[-2:]:
raise IOError("no valid reply from the sensor")
return reply[3:-2]
def read_probe(port):
data = read_registers(port, ADDRESS, 0x03, 0x0003, 2)
return {
"tvoc": struct.unpack(">H", data[0:2])[0], # ppb
"co2_equivalent": struct.unpack(">H", data[2:4])[0], # ppm
}
if __name__ == "__main__":
with serial.Serial(PORT, 9600, bytesize=8, parity="N", stopbits=1, timeout=1) as port:
while True:
print(read_probe(port))
time.sleep(5) Arduino example (Uno, Mega, ESP32, ESP8266, MKR, Pico)
The sketch uses the Agrinovo library: in the Arduino IDE open Sketch > Include Library > Manage Libraries and install "Agrinovo". The library picks the serial port for your board, and the pins are listed at the top of AgrinovoDefaultPort.h. DE and RE of the transceiver go to one output pin.
// Agrinovo TVOC-100 TVOC air quality sensor
// Prints TVOC and CO2 equivalent every 5 seconds.
//
// Sensor terminals
// V+ supply +, 5-12 V DC
// GND supply ground, joined to the board's ground
// A+ RS485 A
// B- RS485 B
//
// The board talks to the sensor through an RS485 transceiver (MAX485 or
// similar). AgrinovoDefaultPort.h lists the serial pins used on each board.
//
// https://agrinovo.io/products/sensors/environmental/tvoc-100-rs485-air-quality-sensor/
#include <Agrinovo.h>
#include <AgrinovoDefaultPort.h>
const int DE_PIN = 4; // transceiver DE and RE, tied together
AgrinovoBus bus(AGRINOVO_PORT, DE_PIN);
AgrinovoTVOC100 sensor(bus); // Modbus address 1
void setup() {
Serial.begin(115200);
agrinovoPortBegin(9600);
bus.begin();
}
void loop() {
if (sensor.read()) {
Serial.print("TVOC: ");
Serial.print(sensor.tvoc(), 0);
Serial.println(" ppb");
Serial.print("CO2 equivalent: ");
Serial.print(sensor.co2Equivalent(), 0);
Serial.println(" ppm");
} else {
Serial.println(sensor.errorText());
}
delay(5000);
} What the examples read
Both examples send one request, function 0x03, 2 registers from 0x0003, and decode these values:
| Value | Unit | Register | Encoding |
|---|---|---|---|
| TVOC | ppb | 0x0003 | Unsigned 16-bit integer, scaled |
| CO2 equivalent | ppm | 0x0004 | Unsigned 16-bit integer, scaled |
Other Modbus tools
The same request works from any Modbus RTU master: pymodbus, minimalmodbus, Node-RED, LabVIEW, a PLC or a third-party data logger with a Modbus port. Use the serial settings, function code and register addresses above.
Logging without writing code
The Omni Genesis controller reads the TVOC-100 and sends the readings to the Agrinovo cloud over the cellular network, where they can be exported or read through the cloud API.
Datasheet reference
Specifications
| Parameter | Specification |
|---|---|
| TVOC Range | 0-60000 ppb |
| TVOC Accuracy | ±1 ppb (0-2008 ppb), ±6 ppb (2008-11110 ppb), ±32 ppb (11110-60000 ppb) |
| CO2eq Range | 400-60000 ppm |
| CO2eq Accuracy | ±1 ppm (400-1479 ppm), ±3 ppm (1479-5144 ppm), ±9 ppm (5144-17597 ppm), ±31 ppm (17597-60000 ppm) |
| Resolution | 1 ppb TVOC, 1 ppm CO2eq |
| Output | RS485, Modbus-RTU |
| Bus Length | Up to 1200 m |
| Supply Voltage | 5-12 V DC |
| Power Consumption | <0.1 W |
| Protection | Built-in surge protection |
| Placement | Indoor, non-condensing |
CO2eq is an equivalent-CO2 air quality value calculated from the VOC measurement. For direct CO2 measurement, pair with a dedicated CO2 sensor.
Communication Settings
| Parameter | Value |
|---|---|
| Protocol | Modbus-RTU |
| Baud Rate | 9600 bps (default); 1200, 2400, 4800, 19200 selectable |
| Data Bits | 8 |
| Parity | None |
| Stop Bits | 1 |
| Error Check | CRC-16 |
| Default Address | 0x01 |
Multiple sensors share one RS485 bus, each with a unique address (1-247).
Register Map
Measurement Registers (Function 0x03 or 0x04)
| Address | Description | Unit |
|---|---|---|
| 0x0003 | TVOC | 1 ppb |
| 0x0004 | CO2eq | 1 ppm |
A register value of 0x8000 indicates a sensing element read error.
Configuration Registers (Function 0x03/0x04 read, 0x06/0x10 write)
| Address | Description | Values |
|---|---|---|
| 0x0064 | Device Address | 1-247, default 1 |
| 0x0065 | Baud Rate | 0: 1200, 1: 2400, 2: 4800, 3: 9600, 4: 19200 |
Reading Data
Read TVOC and CO2eq (2 registers from 0x0003):
Request: 01 03 00 03 00 02 34 0B
Response: 01 03 04 00 7D 02 62 EA A2
Decoding:
| Value | Hex | Decimal | Result |
|---|---|---|---|
| TVOC | 0x007D | 125 | 125 ppb |
| CO2eq | 0x0262 | 610 | 610 ppm |
Address Configuration
Change Address (0x01 → 0x02)
Write to register 0x0064:
01 06 00 64 00 02 49 D4
Broadcast Discovery
With only one sensor on the bus, address 0xFF reads or writes regardless of the configured address. Read the current address:
FF 03 00 64 00 01 D0 0B
Set the address to 0x02 without knowing the current one:
FF 06 00 64 00 02 5C 0A
Change Baud Rate (set 9600)
Write to register 0x0065:
01 06 00 65 00 03 D9 D4
Revision History
| Rev | Date | Changes |
|---|---|---|
| 1.0 | June 2026 | Initial release |
| 1.1 | August 2026 | Layout revision |
| 1.2 | October 2026 | New layout |
Contact
Agrinovo, https://agrinovo.io/products, [email protected], +972 54 688 8148 (direct / WhatsApp). Specifications subject to change without notice.
Questions about wiring or the protocol?
Tell us which board or logger you are using and what you need to measure.