Connecting the PH-110
The probe is an RS485 device, so it needs a transceiver between it and your board. On a computer or a Raspberry Pi that is a USB to RS485 adapter. On a microcontroller it is a MAX485-type module on a hardware serial port. Power the probe from a supply within the voltage range in the table and join its ground to the ground of the transceiver.
RS485 Interface
| Wire Color |
Function |
Description |
| Red |
V+ |
Power (12-24V DC) |
| Black |
GND |
Power Ground |
| Green |
RS485-A |
Data+ |
| Yellow |
RS485-B |
Data- |
Analog Interface
| Wire Color |
Function |
| Red |
Power + |
| Black |
Power - |
| Green |
Signal + |
| Yellow |
Signal - |
Python example (Raspberry Pi, Linux, macOS, Windows)
The script needs only pyserial. It builds the Modbus request itself, checks the CRC of the reply and prints one reading every five seconds. On Windows pass the COM port as the argument.
#!/usr/bin/env python3
"""Read the Agrinovo PH-110 over RS485 Modbus RTU.
Works on a Raspberry Pi or any computer with a USB to RS485 adapter.
Install the serial library once: pip install pyserial
Run: python3 ph_110.py /dev/ttyUSB0
"""
import struct
import sys
import time
import serial
PORT = sys.argv[1] if len(sys.argv) > 1 else "/dev/ttyUSB0"
ADDRESS = 0x01 # the sensor's Modbus address
def crc16(frame: bytes) -> bytes:
crc = 0xFFFF
for byte in frame:
crc ^= byte
for _ in range(8):
crc = (crc >> 1) ^ 0xA001 if crc & 1 else crc >> 1
return struct.pack("<H", crc)
def read_registers(port, address, function, start, count):
request = struct.pack(">BBHH", address, function, start, count)
port.reset_input_buffer()
port.write(request + crc16(request))
reply = port.read(5 + 2 * count)
if len(reply) >= 5 and reply[1] == function | 0x80:
raise IOError(f"sensor returned Modbus error {reply[2]}")
if len(reply) != 5 + 2 * count or crc16(reply[:-2]) != reply[-2:]:
raise IOError("no valid reply from the sensor")
return reply[3:-2]
def read_probe(port):
data = read_registers(port, ADDRESS, 0x03, 0x0000, 1)
return {
"ph": struct.unpack(">H", data[0:2])[0] * 0.01, # pH
}
if __name__ == "__main__":
with serial.Serial(PORT, 9600, bytesize=8, parity="N", stopbits=1, timeout=1) as port:
while True:
print(read_probe(port))
time.sleep(5)
Arduino example (Uno, Mega, ESP32, ESP8266, MKR, Pico)
The sketch uses the Agrinovo library: in the Arduino IDE open Sketch > Include Library > Manage Libraries and install "Agrinovo". The library picks the serial port for your board, and the pins are listed at the top of AgrinovoDefaultPort.h. DE and RE of the transceiver go to one output pin.
// Agrinovo PH-110 industrial pH sensor
// Prints pH every 5 seconds.
//
// Sensor cable
// Red supply +, 12-24 V DC
// Black supply ground, joined to the board's ground
// Green RS485 A
// Yellow RS485 B
//
// The board talks to the sensor through an RS485 transceiver (MAX485 or
// similar). AgrinovoDefaultPort.h lists the serial pins used on each board.
//
// https://agrinovo.io/products/sensors/aqua/ph/ph-110-probe/
#include <Agrinovo.h>
#include <AgrinovoDefaultPort.h>
const int DE_PIN = 4; // transceiver DE and RE, tied together
AgrinovoBus bus(AGRINOVO_PORT, DE_PIN);
AgrinovoPH110 sensor(bus); // Modbus address 1
void setup() {
Serial.begin(115200);
agrinovoPortBegin(9600);
bus.begin();
}
void loop() {
if (sensor.read()) {
Serial.print("pH: ");
Serial.print(sensor.ph(), 2);
Serial.println(" pH");
} else {
Serial.println(sensor.errorText());
}
delay(5000);
}
What the examples read
Both examples send one request, function 0x03, 1 registers from 0x0000, and decode these values:
| Value | Unit | Register | Encoding |
| pH | pH | 0x0000 | Unsigned 16-bit integer, scaled |
Other Modbus tools
The same request works from any Modbus RTU master: pymodbus, minimalmodbus, Node-RED, LabVIEW, a PLC or a third-party data logger with a Modbus port. Use the serial settings, function code and register addresses above.
Logging without writing code
The Omni Genesis controller reads the PH-110 and sends the readings to the Agrinovo cloud over the cellular network, where they can be exported or read through the cloud API.
Datasheet reference
Specifications
| Parameter |
Specification |
| Measurement Range |
0 to 14.00 pH |
| Resolution |
0.01 pH |
| Accuracy |
±0.02 pH |
| Stability |
≤0.02 pH / 24 hours |
| Power Consumption |
≤0.5W |
| Protection Rating |
IP68 |
| Operating Temp |
0 to 70°C |
| Operating Humidity |
≤85% RH |
| Working Pressure |
1.0 MPa |
| Housing Material |
PTFE |
| Start-up Time |
95% of reading within 10 s, 100% within 15 s |
| Update Rate |
New reading every 0.5 s |
Physical Dimensions
| Parameter |
Dimension |
| Total Length |
175 mm |
| Probe Diameter |
28 mm |
| Mounting Thread |
3/4” NPT, top and bottom |
| Cable |
Direct cable, 5 m standard, custom length to order |
| Probe Head |
65 mm |
| Body |
90 mm |
| Tail |
20 mm |
Electrical Characteristics
Each probe is built with one output type, selected when it is ordered.
| Output Type |
Supply Voltage |
| 0 to 2V DC |
12-24 VDC |
| 0 to 5V / 0 to 10V DC |
12-24 VDC |
| 4 to 20mA |
12-24 VDC |
| RS485 |
12-24 VDC |
Communication Settings (RS485)
| Parameter |
Value |
| Protocol |
Modbus-RTU |
| Baud Rate |
9600 bps |
| Data Bits |
8 |
| Parity |
None |
| Stop Bits |
1 |
| Default Address |
0x01 |
Register Map
Measurement Registers (Function 0x03)
| Address |
Description |
Scaling |
| 0x0000 |
pH Value |
Value ÷ 100 |
Configuration Registers (Function 0x06)
| Address |
Description |
Notes |
| 0x0009 |
Intercept/Offset |
Value ÷ 100 |
| 0x0050 |
Slave Address |
0x01 to 0xFE |
| 0x005A |
9.18 pH Cal |
Write 0x000A |
| 0x005B |
6.86 pH Cal |
Write 0x000B |
| 0x005C |
4.00 pH Cal |
Write 0x000C |
Reading pH Value
Request: 01 03 00 00 00 01 84 0A
Response: 01 03 02 02 AE 38 98
Decoding: 0x02AE = 686 → 686 ÷ 100 = 6.86 pH
Three-Point Calibration
| Solution |
Register |
Command |
| 9.18 pH |
0x005A |
01 06 00 5A 00 0A 29 DE |
| 6.86 pH |
0x005B |
01 06 00 5B 00 0B B9 DE |
| 4.00 pH |
0x005C |
01 06 00 5C 00 0C 49 DD |
Analog Output Conversion
Voltage to pH
| Output |
Formula |
| 0 to 2V DC |
pH = V × 7 |
| 0 to 5V DC |
pH = V × 2.8 |
| 0 to 10V DC |
pH = V × 1.4 |
Current to pH
| Output |
Formula |
| 4 to 20mA |
pH = (A - 4) × 0.875 |
Revision History
| Rev |
Date |
Changes |
| 1.0 |
June 2026 |
Initial release |
| 1.1 |
August 2026 |
Layout revision |
| 1.2 |
October 2026 |
New layout; output options, pressure, housing material, cable and start-up time added |
Contact
Agrinovo, https://agrinovo.io/products, [email protected], +972 54 688 8148 (direct / WhatsApp).