ORP-100 with Arduino, ESP32, Raspberry Pi and Python

How to wire the ORP-100 Digital ORP Probe - RS485, Auto Temp Comp to your own microcontroller or computer and read it over RS485 Modbus RTU. The tables are the ones in the datasheet, and both code examples are run against the datasheet example frame before this page is published.

Product page Datasheet (PDF) Datasheet (Markdown) Arduino sketch (.ino) Python script (.py)

ORP-100 Digital ORP Probe - RS485, Auto Temp Comp

Connecting the ORP-100

The probe is an RS485 device, so it needs a transceiver between it and your board. On a computer or a Raspberry Pi that is a USB to RS485 adapter. On a microcontroller it is a MAX485-type module on a hardware serial port. Power the probe from a supply within the voltage range in the table and join its ground to the ground of the transceiver.

Wire Color Function Description
Red V+ Power Supply (12-24V DC)
Black GND Power Ground
Yellow RS485-A Data+
Green RS485-B Data-

Python example (Raspberry Pi, Linux, macOS, Windows)

The script needs only pyserial. It builds the Modbus request itself, checks the CRC of the reply and prints one reading every five seconds. On Windows pass the COM port as the argument.

#!/usr/bin/env python3
"""Read the Agrinovo ORP-100 over RS485 Modbus RTU.

Works on a Raspberry Pi or any computer with a USB to RS485 adapter.
Install the serial library once:  pip install pyserial
Run:  python3 orp_100.py /dev/ttyUSB0
"""
import struct
import sys
import time

import serial

PORT = sys.argv[1] if len(sys.argv) > 1 else "/dev/ttyUSB0"
ADDRESS = 0x01  # the sensor's Modbus address


def crc16(frame: bytes) -> bytes:
    crc = 0xFFFF
    for byte in frame:
        crc ^= byte
        for _ in range(8):
            crc = (crc >> 1) ^ 0xA001 if crc & 1 else crc >> 1
    return struct.pack("<H", crc)


def read_registers(port, address, function, start, count):
    request = struct.pack(">BBHH", address, function, start, count)
    port.reset_input_buffer()
    port.write(request + crc16(request))
    reply = port.read(5 + 2 * count)
    if len(reply) >= 5 and reply[1] == function | 0x80:
        raise IOError(f"sensor returned Modbus error {reply[2]}")
    if len(reply) != 5 + 2 * count or crc16(reply[:-2]) != reply[-2:]:
        raise IOError("no valid reply from the sensor")
    return reply[3:-2]


def read_probe(port):
    data = read_registers(port, ADDRESS, 0x03, 0x0000, 1)
    return {
        "orp": struct.unpack(">h", data[0:2])[0],  # mV
    }


if __name__ == "__main__":
    with serial.Serial(PORT, 9600, bytesize=8, parity="N", stopbits=1, timeout=1) as port:
        while True:
            print(read_probe(port))
            time.sleep(5)

Arduino example (Uno, Mega, ESP32, ESP8266, MKR, Pico)

The sketch uses the Agrinovo library: in the Arduino IDE open Sketch > Include Library > Manage Libraries and install "Agrinovo". The library picks the serial port for your board, and the pins are listed at the top of AgrinovoDefaultPort.h. DE and RE of the transceiver go to one output pin.

// Agrinovo ORP-100 ORP probe
// Prints ORP every 5 seconds.
//
// Sensor cable
//   Red     supply +, 12-24 V DC
//   Black   supply ground, joined to the board's ground
//   Yellow  RS485 A
//   Green   RS485 B
//
// The board talks to the sensor through an RS485 transceiver (MAX485 or
// similar). AgrinovoDefaultPort.h lists the serial pins used on each board.
//
// https://agrinovo.io/products/sensors/aqua/orp/orp-100-probe/

#include <Agrinovo.h>
#include <AgrinovoDefaultPort.h>

const int DE_PIN = 4;  // transceiver DE and RE, tied together

AgrinovoBus bus(AGRINOVO_PORT, DE_PIN);
AgrinovoORP100 probe(bus);  // Modbus address 1

void setup() {
  Serial.begin(115200);
  agrinovoPortBegin(9600);
  bus.begin();
}

void loop() {
  if (probe.read()) {
    Serial.print("ORP: ");
    Serial.print(probe.orp(), 0);
    Serial.println(" mV");
  } else {
    Serial.println(probe.errorText());
  }
  delay(5000);
}

What the examples read

Both examples send one request, function 0x03, 1 registers from 0x0000, and decode these values:

Value Unit Register Encoding
ORP mV 0x0000 Signed 16-bit integer, scaled

Other Modbus tools

The same request works from any Modbus RTU master: pymodbus, minimalmodbus, Node-RED, LabVIEW, a PLC or a third-party data logger with a Modbus port. Use the serial settings, function code and register addresses above.

Logging without writing code

The Omni Genesis controller reads the ORP-100 and sends the readings to the Agrinovo cloud over the cellular network, where they can be exported or read through the cloud API.

Datasheet reference

Specifications

Parameter Specification
Measurement Range -1999 to +1999 mV
Resolution 1 mV
Accuracy ±3 mV
Stability ≤2 mV / 24 hours
Power Consumption ≤0.5W
Supply Voltage 12-24 VDC
Operating Temp 0 to 60°C
Operating Humidity ≤85% RH
Protection IP68
Dimensions Ø28 mm × 160 mm
Mounting Thread 3/4 inch NPT, front and rear

Communication Settings

Parameter Value
Protocol Modbus-RTU
Baud Rate 9600 bps
Data Bits 8
Parity None
Stop Bits 1
Default Address 0x01

Register Map

Measurement Registers (Function 0x03)

Address Description Scaling
0x0000 ORP Value (mV) Direct (signed 16-bit)

Configuration Registers (Function 0x06)

Address Description Notes
0x000A Calibration Offset Signed offset in mV
0x0050 Slave Address 0x01 to 0xFE

Reading ORP Value

Read 1 register from 0x0000:

Request:  01 03 00 00 00 01 84 0A
Response: 01 03 02 02 AE 38 98

Decoding:

Hex Decimal Result
0x02AE 686 686 mV

Negative values use two’s complement. For example, 0xFF9C = -100 mV.

Single-Point Calibration

ORP uses single-point offset calibration via register 0x000A.

Procedure

  1. Prepare an ORP standard solution (e.g. +220 mV)
  2. Clean the electrode with distilled water
  3. Immerse in the standard solution and wait for stabilization
  4. Read the current sensor value
  5. Calculate the offset: offset = standard - reading
  6. Write the offset to register 0x000A

Example

If the standard is +220 mV and the sensor reads +200 mV, the offset is +20:

01 06 00 0A 00 14 A9 C7

If the sensor reads +240 mV, the offset is -20 (0xFFEC in two’s complement):

01 06 00 0A FF EC E9 B5

Address Configuration

Change Address (0x01 → 0x02)

01 06 00 50 00 02 08 1A

Broadcast Discovery

Use address 0xFE with only one device connected.

Revision History

Rev Date Changes
1.0 June 2026 Initial release
1.1 August 2026 Two-page layout; CRC values added to calibration and address examples
1.2 October 2026 New layout

Contact

Agrinovo, https://agrinovo.io/products, [email protected], +972 54 688 8148 (direct / WhatsApp). Specifications subject to change without notice.

Questions about wiring or the protocol?

Tell us which board or logger you are using and what you need to measure.