Greenhouse

Two irrigation systems, two chillers, and the soil temperature that showed which one had failed

A cut flower grower chills its irrigation water. Instrumenting both systems in the root zone rather than at the chillers showed which of the two units was failing, in time to repair it.

Protected cut flower production on two independent irrigation systems 4 min read
An Omni Genesis controller mounted on a greenhouse upright beside a cut flower bed, with sensor cables running down into the soil
A station on the upright, cabled down into the bed it is responsible for.

Results on site

2
systems instrumented identically

The comparison between them is what located the fault

0
sensors on the chillers

The failure was found from its effect in the root zone instead

Repaired
before the crop was affected

As reported by the grower

The challenge
Irrigation water is chilled before it reaches the crop, and nothing measured whether it was still cold when it arrived. With two systems running side by side, a chiller losing performance looked the same as the weather.
What we installed
Each system instrumented identically in its own beds: a tensiometer for soil water tension and a temperature and humidity sensor in the root zone, both on an Omni Genesis controller.
The result
The two systems stopped reading alike, which identified the failing chiller rather than just reporting that something was warm. The grower repaired it before the crop was affected.

The situation

This grower cools its irrigation water before it reaches the crop. Cut flowers are sold on stem quality and uniformity, and the temperature of the root zone is part of how that is produced rather than a variable left to the season, so chillers bring the water to temperature on the way to the beds.

There are two irrigation systems on the site, each with its own chiller, each feeding its own beds. That arrangement is normal and sensible. It also creates a blind spot, because nothing in it reports whether the water is still at temperature when it arrives at the plant. The chillers know whether they are running. They do not know what the roots got.

That distinction matters more than it sounds. A chiller that has failed outright announces itself. A chiller that is slowly losing capacity does not: it runs, it reports normally, and the water leaving it is a little warmer every week. In a greenhouse in warm weather, the resulting drift in the beds looks exactly like the weather, which is the most available explanation and the wrong one.

What was installed

Each system was instrumented in its own beds, identically: a tensiometer reading soil water tension, and a temperature and humidity sensor in the root zone, both wired to an Omni Genesis controller on the greenhouse upright. A small solar panel above it powers the station and reporting is cellular, so the sensors could go where the crop is rather than where power happened to be.

Nothing was attached to the chillers. That was the point.

Why the pair is the instrument

The useful measurement here is not the temperature of either system. It is the difference between them.

A single reading in a single bed is weak evidence. Warm soil in July has too many possible causes to act on: the weather, the time of day, a sensor drifting, an irrigation that did not run. Any of those explains it, and a grower who has run this house for years will reach for the weather first, correctly, most of the time.

Two systems in the same greenhouse, under the same sun, on the same day, should move together. When they stop moving together, every shared explanation is eliminated at once. The weather is shared. The season is shared. The house is shared. What is not shared is the chiller, and that is where the difference has to come from.

This is why the second station was worth installing even though it measures the same quantity as the first. It is not redundancy. The comparison is the instrument.

What the tensiometer is for

The temperature sensors would have found a divergence. The tensiometers are what made it interpretable.

The obvious alternative explanation for one system’s root zone running warmer is that it did not get watered: dry soil heats faster and holds heat differently, so a blocked line or a failed valve produces a similar signature. Soil water tension settles that immediately. Once the record shows that irrigation arrived normally in both systems and the temperatures still parted company, the water itself is what differs, and the chiller is the only thing that sets it.

The grower found the failing unit and repaired it before the crop was affected.

Why it matters

The generalisable part is not about flowers or chillers. It is that you can often measure a machine most reliably by not measuring the machine.

Equipment telemetry reports intent: the pump says it is pumping, the chiller says it is chilling, the dosing unit says it dosed. Each of those is true and none of them describes what reached the plant. A sensor in the root zone is downstream of every failure in the chain, including the ones nobody thought to instrument, and it costs one station instead of a monitoring point on each piece of plant.

And where a farm already runs two of something, instrument both. The second station rarely feels justified, because it measures nothing the first one does not. What it adds is a control: a reading that should agree, and whose disagreement is a fact rather than an interpretation.

From the site

Full view of the monitoring station on a greenhouse upright with its solar panel above and sensor cables running down to the flower bed
Solar panel above, controller on the upright, cables down into the bed. Nothing is attached to the irrigation plant itself.

Hardware in this deployment

Every sensor below connects to the same controller. That is what makes a mixed site possible.

Questions about this deployment

Why would a flower grower chill the irrigation water?

To control the temperature of the root zone rather than only the air. Roots respond to the temperature of the medium they sit in, and in a warm climate irrigation water that has sat in pipes and tanks arrives warm enough to move that temperature. For a crop sold on stem quality and uniformity, root zone conditions are part of the specification rather than a background variable, so the water is brought to temperature before it reaches the beds.

Why measure in the soil instead of putting a sensor on the chiller?

Because a chiller's own status tells you what the machine believes it is doing, not what arrives at the plant. A unit can be running, reporting normally, and still be losing capacity, and the water can pick up heat between the plant room and the bed. Measuring in the root zone measures the thing the crop actually experiences, which is downstream of the chiller, the pipework and everything else in between.

Why does having two systems make the fault findable?

Because it turns an absolute reading into a comparison, and a comparison is far harder to argue with. A single warm reading has many explanations: hot week, sunny day, sensor drift, an irrigation that did not run. Two systems in the same house under the same weather should track each other. When they stop tracking each other, the weather is ruled out and the difference points at the one thing that is not shared between them.

What does the tensiometer add that temperature alone does not?

It rules out the simplest explanation. If the root zone in one system warms up, the first question is whether that system was irrigated at all, because dry soil warms faster and a missed irrigation would produce a similar picture. Soil water tension answers that directly. Once you can see that water arrived normally and the temperature still diverged, the remaining explanation is the temperature of the water itself.

Could you not just alarm on the chiller directly?

You can, and it is worth doing, but it answers a different question. A chiller alarm tells you when the unit has failed outright. It is much weaker at telling you when a unit is gradually losing performance while still reporting itself as running, which is the failure mode that does damage quietly. The root zone measurement catches degradation because it measures the result rather than the equipment's opinion of itself.

How is the station powered in a greenhouse?

A small solar panel on the same upright as the controller, with cellular reporting. That keeps the installation independent of where power happens to be available in the house, which matters because the sensors have to go where the crop is rather than where a socket is.

Planning something similar?

Tell us what needs monitoring and we will scope a right-sized system with you.

Send a message instead